Section 04 — Carbon Accounting & Abatement

Campus Greenhouse Gas Footprint & Avoided Emissions

"In 2024, VIT's gross greenhouse gas emissions totaled 30,757 tonnes CO₂e—with grid electricity comprising 77.9%. Campus vegetative sinks sequester 2,814 t CO₂/yr, yielding net emissions of 27,943 t CO₂e. Clean energy interventions currently avoid 14,500+ tonnes of additional emissions annually."
30,757 t CO₂e
Gross Annual Greenhouse Footprint (Scope 1 + Scope 2)
Environmental Audit 2024, p. 21
2,814.4 t/yr
Sequestration by Campus Trees, Lawn & Open Soil
Green Audit 2023, p. 54
27,942.8 t/yr
Net Annual Campus Emissions (Gross Footprint − Natural Sinks)
Environmental Audit 2024, p. 21
13,103 t/yr
Emissions Avoided Annually via Offsite Wind & Solar Procurement
Calculated @ 0.813 kg/kWh

1. Gross Emissions Breakdown by Source (2024)

Grid-supplied electricity dominates the university's operational emissions footprint. While fuel combustion in 31 backup diesel generators (2,30,000 L/yr), student shuttles (2,83,057 L/yr), and kitchen LPG (16.61 lakh L/yr) contributes 4,246 tonnes CO₂e, purchased electricity represents 23,968 tonnes CO₂e.

Fig. 4.1 — Source distribution of annual gross campus CO₂e emissions (30,757 tonnes total). Source: Environmental Audit Report (2024), p. 21.

2. Avoided Emissions from Sustainable Infrastructure

VIT has invested in four major technical systems that actively displace thermal electricity and direct combustion:

Intervention Technology Details Energy Saved (Annual) Avoided CO₂ (Annual) Cost Saved (₹/yr)
Contracted Wind Wheeling 1.22 Cr kWh purchased from Bharat Enterprises & BBK Shoes 1,22,00,000 kWh 9,918.6 t ₹3.63 Cr
Rooftop Solar PV 2.81 MWp rooftop panels producing 37.97 lakh units/yr 37,97,955 kWh 3,087.7 t ₹2.56 Cr
District Cooling System 5,500 TR central chiller plant vs decentralised split ACs 5,49,418 kWh 1,531.0 t ₹44.2 Lakh
Heat Pump Hot Water SES 12T Heat Pumps (COP 4.0) vs electrical resistance 15,29,775 kWh 1,392.1 t ₹1.23 Cr
Gandhi Block Cooling Radiant slab cooling + Indirect Evaporative Cooling (IEC) 3,14,160 kWh 12.6 t ₹21.9 Lakh
Table 4.1 — Clean technology displacement analysis. Calculated based on 2020 Energy Audit and 2024 Environmental Audit certified savings.

3. Point-Source Emitters & Laboratory Verification

Beyond utility electricity, specific engineering disciplines host localized emission sources identified during field audits:

  • Automotive & IC Engine Labs (SMEC): Houses multi-cylinder test rigs and dynamometers burning diesel and petrol fuel blends for experimental combustion analysis. Exhaust is routed through dedicated scrubbers and elevated flues.
  • Chemical & Process Engineering Labs (SCHEME / SMV): Operates batch reaction kettles, solvent recovery columns, and thermal units. Organic chemical wastes are safely sequestered in cement chambers and handed to TNPCB-authorized recyclers.
  • Emergency DG Sets (31 units, 16.9 MVA): Diesel backup capacity operated during grid failures and monsoon emergencies. Fitted with acoustic enclosures and stack heights up to 24 meters in compliance with CPCB air pollution guidelines.
  1. Scope 1 Fuel Emissions: Diesel generators (2,30,000 L) and transport diesel (2,83,057 L) calculated at 0.00333 t CO₂/L. LPG (16,61,186 L) calculated at 0.00152 t CO₂/L. Environmental Audit Report 2024, p. 21.
  2. Scope 2 Grid Factor: The audit report applies a conservative 0.813 kg CO₂/kWh factor reflecting Tamil Nadu's legacy thermal fleet, whereas the CEA Version 19 CO₂ baseline for the integrated Southern regional grid documents 0.716 kg CO₂/kWh due to rising regional wind and solar penetration.